Seattle.gov Home Page City Services Staff Directory [WEB GRAPHIC] About Seattle.gov City Contacts
Seattle.gov Home Page
 SEARCH: 
Seattle.gov This Department
Link to DPD Home Page Shaping and protecting Seattle's built and natural environment Link to DPD Home Page Link to About Us Link to Contact Us Diane Sugimura, DPD Director
  •  
  • Planning
  • Permits
  • Compliance
  • Online Tools
  • Resource Center
  •  
Seattle Energy Code
Reference Standard-29

Nonresidential Building Design By Systems Analysis

SECTION 1 - SCOPE

1.1 General

SECTION 2 - GENERAL PRINCIPLES AND REQUIREMENTS

2.1 Energy Analysis
2.2 Design
2.3 Analysis Procedure
2.4 Calculation Procedure
2.5 Documentation

SECTION 3 -- SPECIFIC MODELING ASSUMPTIONS

3.1 Orientation and Shape
3.2 Internal Loads

3.2.1 Occupancy
3.2.2 Lighting
3.2.3 Receptacle

3.3 Envelope

3.3.1 Insulation and Glazing
3.3.2 Infiltration
3.3.3 Envelope and Ground Absorptivities
3.3.4 Window Treatment
3.3.5 Shading

3.4 HVAC Systems and Equipment

3.4.1 HVAC Zones
3.4.2 Process Equipment Sizing
3.4.3 HVAC Equipment Sizing
3.4.4 Variable Speed

3.5 Service Water Heating
3.6 Controls

3.6.1
3.6.2
3.6.3
3.6.4
3.6.5

TABLE 3-1 -- Acceptable Occupancy Densities, Receptacle Power Densities and Service Hot Water Consumption

TABLE 3-2A -- Assembly Occupancy

TABLE 3-2B -- Health Occupancy

TABLE 3-2C -- Hotel/Motel Occupancy

TABLE 3-2D -- Light Manufacturing Occupancy

TABLE 3-2E -- Office Occupancy

TABLE 3-2F -- Parking Garage Occupancy

TABLE 3-2G -- Restaurant Occupancy

TABLE 3-2H -- Retail Occupancy

TABLE 3-2I -- School Occupancy

TABLE 3-2J -- Warehouse Occupancy

TABLE 3-3 -- HVAC Systems of Prototype Buildings

TABLE 3-3 (cont.) -- HVAC System Descriptions for Prototype Buildings

SECTION 4 -- SUGGESTED SOFTWARE FOR SYSTEMS ANALYSIS APPROACH

4.1 Programs Acceptable for Projects for Full-Year Hourly Analysis

4.2 Programs only Acceptable for Commercial Buildings 25,000 Square Feet or Less




REFERENCE STANDARD-29
NONRESIDENTIAL BUILDING DESIGN BY SYSTEMS ANALYSIS

**Form Building Envelope Checklist (ENV-CHK), Form Mechanical Checklist (MECH-CHK), Form Complex Mechanical Checklist (MECH-COMP), Form Lighting Checklist (LTG-CHK), Form Motor Checklist (MECH-MOT), Form Energy End Use Summary, Form Design Parameter Comparison **

Section 1 - Scope

1.1 General: This Standard establishes design criteria in terms of total energy consumption of a building, including all of its systems. General principles and requirements are outlined in Section 2. Specific modeling assumptions are listed in Section 3.

The building permit application for projects utilizing this Standard shall include in one submittal all building and mechanical drawings and all information necessary to verify that the design for the project corresponds with the annual energy analysis. If credit is proposed to be taken for lighting energy savings, then electrical drawings shall also be included with the building permit application.

Due to the various assumptions that are necessary, the results of the analysis shall not be construed as a guarantee of the actual energy performance of the project.

Section 2 - General Principles and Requirements

2.1 Energy Analysis: Compliance with this Standard will require an analysis of the annual energy usage, hereinafter called an annual energy analysis.

A building designed in accordance with this Standard will be deemed as complying with this Code, if

  1. The calculated annual energy consumption is not greater than that of a corresponding "standard design," as defined below and in Section 3, and;
  2. Whose enclosure elements and energy-consuming systems comply with Sections 1310 through 1314, 1410 through 1416, 1440 through 1443, 1450 through 1454 and 1510 through 1513. Buildings shall only vary from those requirements in Sections 1330 through 1334, 1432 through 1439 and 1530 through 1532 where those variations have been accurately and completely modeled. Where variations are not specifically analyzed, the building shall comply with these requirements.

For a proposed building design to be considered similar to a "standard design," it shall utilize the same energy source(s) for the same functions and have equal floor area and the same ratio of envelope area to floor area, environmental requirements, occupancy, climate data and usage operational schedule. Inputs to the energy analysis relating to occupancy and usage shall correspond to the expected occupancy and usage of the building.

Except as noted below, the systems identified, and, to the extent possible, the assumptions made in assigning energy inputs to each system, shall be the same for the standard design and the proposed design. When electrically driven heat pumps, other than multiple units connected to a common water loop, are employed to provide all or part of the heat for the proposed design, the standard design shall also, for the purposes of the analysis, assume that electrically driven heat pump, in conformance with Chapter 14 of the Code and having capacity at least as great as those used in the proposed design are employed.

2.2 Design: The standard design and the proposed design shall be designed on a common basis as specified herein:

  1. The comparison shall be expressed as kBtu input per square foot of conditioned floor area per year at the building site. Buildings which use electricity as the only fuel source, comparisons may be expressed in kWh. When converting electricity in kWh to kBtu a multiplier of 3.413 kWh/kBtu shall be used.
  2. If the proposed design results in an increase in consumption of one energy source and a decrease in another energy source, even though similar sources are used for similar purposes, the difference in each energy source shall be converted to equivalent energy units for purposes of comparing the total energy used.

2.3 Analysis Procedure: The analysis of the annual energy usage of the standard and the proposed building and system design shall meet the following criteria:

  1. The building heating/cooling load calculation procedure used for annual energy consumption analysis shall be detailed to permit the evaluation of effect of factors specified in Section 2.4.
  2. The calculation procedure used to simulate the operation of the building and its service systems through a full-year operating period shall be detailed to permit the evaluation of the effect of system design, climatic factors, operational characteristics and mechanical equipment on annual energy usage. Manufacturer's data or comparable field test data shall be used when available in the simulation of systems and equipment. The calculation procedure shall be based upon 8,760 hours of operation of the building and its service systems and shall utilize the design methods, specified in Standard RS-1 listed in Chapter 7 of the Code or in other programs approved by the building official.

2.4 Calculation Procedure: The calculation procedure shall cover the following items:

  1. Design requirements--Design heating conditions and design cooling conditions as defined in Chapter 2 of the Code.
  2. Climatic data--Coincident hourly data for temperatures, solar radiation, wind and humidity of typical days in the year representing seasonal variation.
  3. Building data--Orientation, size, shape, mass, air and heat transfer characteristics.
  4. Operational characteristics--Temperature, humidity, ventilation, illumination and control mode for occupied and unoccupied hours.
  5. Mechanical equipment--Design capacity and part load profile.
  6. Building loads--Internal heat generation, lighting, equipment and number of people during occupied and unoccupied periods.

2.5 Documentation: All analyses submitted shall be accompanied by an energy analysis comparison report. The report shall provide technical detail on the two building and system designs and on the data used in and resulting from the comparative analysis to verify that both the analysis and the designs meet the criteria of Section 1.

The calculation procedure for the standard design and the proposed design shall separately identify the calculated annual energy consumption for each different occupancy type, if possible, for each of the following end uses:

a. Interior lighting;
b. Parking lighting;
c. Exterior lighting;
d. Space heating;
e. Space cooling;
f. Interior ventilation/fans;
g. Parking ventilation/fans;
h. Exhaust fans;
i. Service water heating;
j. Elevators; and
k. Appliances.

Energy consumption of the following items shall be included but is not required to be separated out by each individual item.

  1. Office equipment;
  2. Refrigeration other than comfort cooling;
  3. Cooking; and
  4. Any other energy-consuming equipment.

The specifications of the proposed building project used in the analysis shall be as similar as is reasonably practical to those in the plans submitted for a building permit.

Section 3 -- Specific Modeling Assumptions

The specific modeling assumptions consist of methods and assumptions for calculating the standard energy consumption for the standard building and the proposed energy consumption of the proposed design. In order to maintain consistency between the standard and the proposed design energy consumptions, the input assumptions in this section shall be used.

"Prescribed" assumptions shall be used without variation. "Default" assumptions shall be used unless the designer can demonstrate that a different assumption better characterizes the building's use over its expected life. Any modification of a default assumption shall be used in modeling both the standard building and the proposed design unless the designer demonstrates a clear cause to do otherwise.

3.1 Orientation and Shape: The standard building shall consist of the same number of stories and gross floor area for each story as the proposed design. Each floor shall be oriented exactly as the proposed design. The geometric form shall be the same as the proposed design.

3.2 Internal Loads: Internal loads shall be modeled as noted in the following parts of Section 3.2. The systems specified for calculating the standard energy consumption in Section 3.2 are intended only as constraints in calculating the consumption. They are not intended as requirements or recommendations for systems to be used in the proposed building or for the calculation of the proposed energy consumption.

3.2.1 Occupancy: Occupancy schedules shall be default assumptions. The same assumptions shall be made in computing proposed energy consumption as were used in calculating the standard energy consumption. Occupancy levels vary by building type and time of day. Table 3-1 establishes the density presented as ft2/person of conditioned floor area that will be used by each building type. Table 3-2 establishes the percentage of the people that are in the building by hours of the day for each building type.

3.2.2 Lighting **CAM 405, Form Lighting Summary Form, Website Lighting Design Lab** : The interior and exterior lighting power allowance for calculating the standard energy consumption shall be determined from Sections 1531 and 1532. The lighting power used to calculate the proposed energy consumption shall be the actual lighting power of the proposed lighting design. Exempt lighting in the standard design shall be equal to the exempt lighting in the proposed design.

Lighting levels in buildings vary based on the type of uses within buildings, by area and by time of day. Table 3-2 contains the lighting energy profiles which establish the percentage of the lighting load that is switched ON in each prototype or reference building by hour of the day. These profiles are default assumptions and can be changed if required when calculating the standard energy consumption to provide, for example, a 12 hour rather than an 8 hour work day or to reflect the use of automatic lighting controls. The lighting schedules used in the standard and proposed designs shall be identical and shall reflect the type of controls to be installed in the proposed design. The controls in the proposed design shall comply with the requirements in Section 1513 and no credit shall be given for the use of any additional controls, automatic or otherwise.

3.2.3 Receptacle: Receptacle loads and profiles are default assumptions. The same assumptions shall be made in calculating proposed energy consumption as were used in calculating the standard energy consumption. Receptacle loads include all general service loads that are typical in a building. These loads should include additional process electrical usage but exclude HVAC primary or auxiliary electrical usage. Table 3-1 establishes the density in W/ft2 to be used. The receptacle energy profiles shall be the same as the lighting energy profiles in Table 3-2. This profile establishes the percentage of the receptacle load that is switched ON by hour of the day and by building type.

3.3 Envelope

3.3.1 Insulation and Glazing: **CAM 403; Website NFRC** Glazing area and U-factor of the standard building envelope shall be determined by using the Target UA requirements of Equation 13-1 and U-factor values in Table 13-1 or 13-2. The glazing solar heat gain coefficient (SHGC) or shading coefficient of the standard building shall be the lesser of 0.65 and the SHGC required by Table 13-1 or 13-2 for the vertical or overhead glazing area for the appropriate wall type. The opaque area U-factors of the standard building shall be determined by using the Target UA requirements from Equation 13-1 including the appropriate mass for walls, except that the walls in the standard design shall be metal stud walls. The insulation characteristics and glazing area are prescribed assumptions for the standard building for calculating the standard energy consumption. In the calculation of the proposed energy consumption of the proposed design, the envelope characteristics of the proposed design shall be used. The standard design shall use the lesser of the glazing area of the proposed design or the maximum glazing areas listed in Tables 13-1 or 13-2 for the appropriate use. The distribution of vertical glazing in the gross wall area of the standard design shall be equal to the distribution of vertical glazing in the proposed design or shall constitute an equal percentage of gross wall area on all sides of the standard building. The distribution of overhead glazing in the gross roof/ceiling area of the standard design shall be equal to the distribution of overhead glazing in the proposed design. The distribution of doors in the gross opaque wall area of the standard design shall be identical to the distribution of doors in the proposed design.

3.3.2 Infiltration: For standard and proposed buildings, infiltration assumptions shall be equal.

3.3.3 Envelope and Ground Absorptivities: For the standard building, absorptivity assumptions shall be default assumptions for computing the standard energy consumption and default assumptions for computing the proposed energy consumption. The solar absorptivity of opaque elements of the building envelope shall be assumed to be 70%. The solar absorptivity of ground surfaces shall be assumed to be 80% (20% reflectivity).

3.3.4 Window Treatment: No draperies or blinds shall be modeled for the standard or proposed building.

3.3.5 Shading: For standard building and the proposed design, shading by permanent structures and terrain shall be taken into account for computing energy consumption whether or not these features are located on the building site. A permanent fixture is one that is likely to remain for the life of the proposed design. Credit may be taken for external shading devices that are part of the proposed design.

3.4 HVAC Systems and Equipment: For the standard building, the HVAC system used shall be the system type used in the proposed design. If the proposed HVAC system type does not comply with Sections 1432 through 1439, the standard design system shall comply in all respects with those sections.

EXCEPTION: When approved by the building official, a A prototype HVAC system may be used, if the proposed design system cannot be modified to comply with Sections 1422 and 1432 through 1439, as a standard design. Use of prototype HVAC systems shall only be permitted for the building types listed below. For mixed-use buildings, the floor space of each building type is allocated within the floor space of the standard building. The specifications and requirements for the HVAC systems of prototype buildings shall be those in Table 3-3.

1. assembly
2. health/institutional
3. hotel/motel
4. light manufacturing
5. office (business)
6. restaurant
7. retail (mercantile)
8. school (educational)
9. warehouse (storage)

3.4.1 HVAC Zones: HVAC zones for calculating the standard energy consumption and proposed energy consumption shall consist of at least four perimeter and one interior zone per floor, with at least one perimeter zone facing each orientation. The perimeter zones shall be fifteen feet in width or one-third the narrow dimension of the building when this dimension is between 30 and 45 feet inclusive or half the narrow dimension of the building when this dimension is less than thirty feet.

EXCEPTIONS:

  1. Building types such as assembly or warehouse may be modeled as a single zone if there is only one space.
  2. Thermally similar zones, such as those facing one orientation on different floors, may be grouped together for the purposes of either the standard or proposed building simulation.

3.4.2 Process Equipment Sizing: Process sensible and latent loads shall be equal in calculating both the standard energy consumption and the proposed energy consumption. The designer shall document the installation of process equipment and the size of process loads.

3.4.3 HVAC Equipment Sizing: The equipment shall be sized to include the capacity to meet the process loads. For calculating the proposed energy consumption, actual air flow rates and installed equipment size shall be used in the simulation. Equipment sizing in the simulation of the proposed design shall correspond to the equipment intended to be selected for the design and the designer shall not use equipment sized automatically by the simulation tool.

Equipment sizing for the standard design shall be based on the same as the proposed design or lesser sizing ratio of installed system capacity to the design load for heating and for cooling.

Chilled water systems for the standard building shall be modeled using a reciprocating chiller for systems with total cooling capacities less than 175 tons, and centrifugal chillers for systems with cooling capacities of 175 tons or greater. For systems with cooling capacities of 600 tons or more the standard energy consumption shall be calculated using two centrifugal chillers, lead/lag controlled. Chilled water shall be assumed to be controlled at a constant 44°F temperature rise, from 44°F to 56°F, operating at 65% combined impeller and motor efficiency. Condenser water pumps shall be sized using a 10°F temperature rise, operating at 60% combined impeller and motor efficiency. The cooling tower shall be an open circuit, centrifugal blower type sized for the larger of 85°F leaving water temperature or 10°F approach to design wetbulb temperature. The tower shall be controlled to provide a 65°F leaving water temperature whenever weather conditions permit, floating up to design leaving water temperature at design conditions.

3.4.4 Fans: The power of the combined fan system per air volume at design conditions (w/cfm) of the proposed design shall be equal to that of the The standard design shall comply with the following.

3.4.4.1 Fan System Power Limitation: Each HVAC system at fan system design conditions shall not exceed the allowable fan system motor nameplate hp [Option 1] or fan system bhp [Option 2] as shown in the Fan Power Limitation table. This includes supply fans, return/relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability.

Fan Power Limitation
   Limit  Constant Volume  Variable Volume
Option 1: Fan System Motor Nameplate hp Allowable Nameplate Motor hp  hp≤ CFMS*0.0011 hp≤ CFMS*0.0015
Option 2: Fan System bhp Allowable Fan System bhp  bhp≤ CFMS * 0.00094 + A  bhp≤ CFMS * 0.0013 + A


where:

fan brake horsepower = the horsepower delivered to the fan’s shaft. Brake horsepower does not include the mechanical drive losses (belts, gears, etc.).

fan system design conditions = operating conditions that can be expected to occur during normal system operation that result in the highest supply airflow rate to conditioned spaces served by the system.

fan system bhp = the sum of the fan brake horsepower of all fans that are required to operate at fan system design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors.

fan system motor nameplate hp = the sum of the motor nameplate horsepower of all fans that are required to operate at design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors. nameplate horsepower = the nominal motor horsepower rating stamped on the motor nameplate.

CFMS = the maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute

hp = the maximum combined motor nameplate horsepower

bhp = the maximum combined fan brake horsepower

A = Sum of [PD x CFMD / 4131] where:

PD = Each applicable pressure drop adjustment from the table below in in. w.c.

CFMD = the design air flow through each applicable device from the table below in cubic feet per minute

EXCEPTIONS:

  1. Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control may use variable volume fan power limitation.
  2. Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
  3. Fans exhausting air from fume hoods. (Note: If this exception is taken, no related exhaust side credits shall be taken from the table below and the Fume Exhaust Exception Deduction shall be taken from the table below)
Fan Power Limitation Pressure Drop Adjustment
Device Adjustment
Credits
Fully ducted return and/or exhaust air systems 0.5 in. w.c.
Return and/or exhaust air flow control devices 0.5 in. w.c.
Exhaust filters, scrubbers, or other exhaust treatment. Pressure drop of device at fan system design condition
Particulate filtration credit: MERV 9 thru 12 0.5 in. w.c.
Particulate filtration credit: MERV 13 thru 15 0.9 in. w.c.
Particulate filtration credit: MERV 16 and greater and electronically enhanced filters Pressure drop calculated at 2x clean filter pressure drop at fan system design condition
Carbon and other gas-phase air cleaners Clean filter pressure drop at fan system design condition
Heat recovery device Pressure drop of device at fan system design condition
Evaporative humidifier/cooler in series with another cooling coil Pressure drop of device at fan system design condition
Sound attenuation section 0.15 in. w.c.
Deductions
Fume hood exhaust exception (required if 1438.2.1 exception (c) is taken)  -1.0 in. w.c.


3.4.4.2 Motor Nameplate Horsepower : Each HVAC system at fan system design conditions shall not exceed the allowable fan system motor nameplate hp [Option 1] or fan system bhp [Option 2] as shown in the Fan Power Limitation table. This includes supply fans, return/relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability.

EXCEPTIONS:

  1. For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50% of the brake horsepower, the next larger nameplate motor size may be selected.
  2. For fans 6 bhp and larger, where the first available motor larger than the brake horsepower has a nameplate rating within 30% of the brake horsepower, the next larger nameplate motor size may be selected.

3.4.4.3 Variable speed: Variable air volume fan systems in the standard building shall be variable speed.

3.5 Service Water Heating: The service water heating loads for prototype buildings are defined in terms of Btu/person-hour in Table 3-1. The values in the table refer to energy content of the heated water. The service water heating loads from Table 3-1 are default for all buildings. The same service-water-heating load assumptions shall be made in calculating proposed energy consumption as were used in calculating the standard energy consumption. The service water heating system for the standard building shall be modeled as closely as possible as if it were designed in accordance with RS-11 and meeting all the requirements of Sections 1440 through 1443.

3.6 Controls

3.6.1: All occupied conditioned spaces in standard and proposed design buildings in all climates shall be simulated as being both heated and cooled.

EXCEPTIONS:

  1. If a building or portion of a building is to be provided with only heating or cooling, both the standard building and the proposed design shall be simulated using the same assumptions.
  2. If warehouses are not intended to be mechanically cooled, both the standard and proposed energy consumption shall be modeled assuming no mechanical cooling.

3.6.2: Space temperature controls for the standard building, shall be set at 70° F for space heating and 75° F for space cooling, with a deadband in accordance with Section 1412.2. The system shall be OFF during off-hours according to the appropriate schedule in Table 3-2, except that the heating system shall cycle ON if any space should drop below the night setback setting 55° F. There shall be no similar setpoint during the cooling season. Lesser deadband ranges may be used in calculating the proposed energy consumption.

EXCEPTIONS:

  1. Setback shall not be modeled in determining either the standard or proposed energy consumption if setback is not realistic for the proposed design such as a facility being operated 24 hours/day. For instance, health facilities need not have night setback during the heating season.
  2. If deadband controls are not to be installed, the proposed energy consumption shall be calculated with both heating and cooling thermostat setpoints set to the same value between 70° F and 75° F inclusive, assumed to be constant for the year.

3.6.3: When providing for outdoor air ventilation when calculating the standard energy consumption, controls shall be assumed to close the outside air intake to reduce the flow of outside air to 0.0 cfm during " setback" and "unoccupied" periods. Ventilation using inside air may still be required to maintain scheduled setback temperature. Outside air ventilation, during occupied periods, shall be as required by the Washington State Ventilation and Indoor Air Quality Code, Chapter 51-13 WAC. **CAM 406**

3.6.4: If humidification is to be used in the proposed design, the same level of humidification and system type shall be used in the standard building.

3.6.5: There shall be no credit in the proposed design for control of parking garage ventilation.

TABLE 3-1 - Acceptable Occupancy Densities, Receptacle Power Densities and Service Hot Water Consumption 1

TABLE 3-2A - Assembly Occupancy1

TABLE 3-2B - Health Occupancy1

TABLE 3-2C - Hotel/Motel Occupancy1

TABLE 3-2D - Light Manufacturing Occupancy1

TABLE 3-2E - Office Occupancy1

TABLE 3-2F - Parking Garage Occupancy1

TABLE 3-2G - Restaurant Occupancy1

TABLE 3-2H - Retail Occupancy1

TABLE 3-2I - School Occupancy1

TABLE 3-2J - Warehouse Occupancy1

TABLE 3-3 - HVAC Systems of Prototype Buildings3

TABLE 3-3 (Continued) - HVAC System Descriptions for Prototype Buildings1

SECTION 4 -- SUGGESTED SOFTWARE FOR SYSTEMS ANALYSIS APPROACH

Program Name Source
Blast 3.0 (Level 334) Blast Support Office
University of Illinois
Dept. of Mechanical and Industrial Engineering
1206 W. Green Street, Room 140, MEB
Urbana, Il 61801
(217) 244-8182
 
DOE 2.1E Energy Science and Technology Software Center
PO Box 1220
Oakridge, TN 37831-1020
(423) 576-2606
 
DOE 2.1E or DOE 2.2 James J. Hirsch and Associates
Building Performance Analysis Software & Consulting
12185 Presilla Rd.
Camarillo, CA 93012-9243
(805) 532-1045
 
Energy Plus Kathy Ellington
Lawrence Berkeley National Laboratory
Building 90, Room 3147
Berkeley, CA 94720-0001
(510) 486-5711
 
ESAS Ross Meriweather Consulting, Engineering
3315 Outrider
San Antonio, TX 78247-4405
(210) 490-7081
 
ESP-II Automated Procedures for Engineering Consultants, Inc.
40 W. 4th Centre, Suite 2100
Dayton, OH 45402
(937) 228-2602
 
HAP 3.24 Carrier Building Systems and Services
3215 S. 116th Street, Suite 133
Tukwila, WA 98168
(206) 439-0097
 
Trace 600 Version 18.11 or
Trace 700
The Trane Co.
3600 Pammel Creek Rd.
Lacrosse, WI 54601
(608) 787-3926
Last Updated: January 9, 2008
General Information

  • 2006 Seattle Energy Code Update
  • Residential Tips
  • Nonresidential Tips
  • Energy Efficiency Information Links
  • Seattle Energy Code History
  • Mayor's Climate Protection Initiative
Resources
  • Forms - Residential
  • Forms - Nonresidential
  • Client Assistance Memos - Energy related
  • Director's Rules
    - Energy related
  • Seattle EnvStd - Nonresidential Building Envelope Compliance Tool

Want to Download or Print the Energy Code?
Click here for information on downloading the Seattle insert pages for the 2006 Washington State Energy Code and the 2006 Washington State Energy Code.

Technical Backup

Helpful Links

Getting A Permit

Department of Planning and Development (DPD)
DPD Home | About DPD | Contact DPD | Search DPD | Site Index
Seattle.gov: Services | Departments | Staff Directory | Mayor | City Council
Copyright © 1995-2009 City of Seattle Questions/Complaints | Privacy & Security Policy